Pickup verification (ig mode) – Basler Electric BE1-11m User Manual

Page 374

Advertising
background image

362

9424200996 Rev L

Step 7: (Optional.) Repeat steps 1 through 6 for 51-2, 51-3, 51-4, and 51-5.

Step 8: (Optional.) Repeat steps 1 through 7 with CT Circuit 2 as the source for protection systems

equipped with two sets of CTs. In step 3, replace D1 with F1, D2 with F2, etc.

Pickup Verification (IG Mode)

Step 1: Use BESTCOMSPlus to send the operational settings in Table 158 to the BE1-11m. Reset all

targets.

Table 158. Operational Settings (IG Mode)

Setting

Value

BESTCOMSPlus Screen

Description

Ground CT
Ratio

1

System Parameters, Sensing
Transformers

Sets ground CT ratio to 1

Element
Mode

IG

Protection, Current, Instantaneous
Overcurrent (51-1)

Enables 51-1 function for
IG mode

Source

CT Circuit 1

Protection, Current, Instantaneous
Overcurrent (51-1)

Selects CT circuit 1 as the
source

51-1 IND
GND

Enabled

Target Configuration, Targets

Enables IND GND target
for 51-1

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 262.

Blocking is disabled.

OUT1 closes for 51-1 Trip.

OUT2 closes for 51-1 Pickup.

Fault recording is enabled.

Figure 262. BESTlogicPlus Settings (IG Mode)

Step 3: Use BESTCOMSPlus to open the Protection, Current, Inverse Overcurrent (51-1) screen and

send the low range test settings (minimum pickup setting) to the BE1-11m for your sensing input
type in Table 159.

Step 4: Prepare to monitor the 51-1 function operation. Operation can be verified by monitoring OUT2

(see Figure 262).

Step 5: Connect a current source to terminals D7 and D8 (IG).

Step 6: Slowly increase the ground current until OUT2 closes and record the pickup. Verify that there is

a 51-1-IND GND target on the front-panel display. Slowly decrease the applied current until
OUT2 opens and record the dropout.

Step 7: Repeat step 6 for the middle and high range pickup settings for your sensing input type. Record

the results.

Step 8: (Optional.) Repeat steps 1 through 7 for settings group 1, 2, and 3.

Step 9: (Optional.) Repeat steps 1 through 8 for 51-2, 51-3, 51-4, and 51-5.

Inverse Overcurrent (51) Test