Procedure 2 – Basler Electric BE1-11m User Manual

Page 513

Advertising
background image

9424200996 Rev L

501

5.

Open the RTD Module plugin in BESTCOMSPlus.

6.

Pull down the Communication menu and select New Connection

 RTD Module. The RTD Module

Connection screen appears.

7.

Under Device Discovery, click the Ethernet button to scan for connected devices.

8.

After scanning for connected devices, the Device Discovery screen appears.

9.

Use the computer mouse to highlight the desired RTD module and click the Configure button.

10.

The Configure - RTD Module screen appears. The BE1-11m uses the Device Address (Remote
Module ID) to communicate with the RTD module. The RTD module comes with a default address of
255 (module disabled). Enter the desired device address between 1 and 254.

11.

Assign an IP Address to the RTD module by entering an address in the same range as the IP
address of the PC recorded in Step 4. For example, if the IP address recorded in Step 4 was
169.254.153.248, you could enter 169.254.153.150 or 169.254.153.45. (The range is 1 to 255.)

12.

The PC and RTD module must have the same Subnet Mask and Default Gateway. Assign the Subnet
Mask and Default Gateway to the RTD module using the values of the PC recorded in Step 4.

13.

Click Send to Device. A password is required. The default password is “OEM”. Click Close.

14.

Click Cancel on the Device Discovery screen.

15.

Cycle power to the RTD module to activate the new IP address.

Verify RTD Module Communication and Save a Settings File

16.

To verify that the IP address of the RTD module was correctly configured or to save a settings file for
the RTD module, click the Ethernet button under Device Discovery to scan for connected devices.

17.

After scanning for connected devices, the Device Discovery screen appears.

18.

Use the computer mouse to highlight the desired RTD module and click the Connect button. If the
Device Needs Activated screen appears, refer to RTD Module Plugin for BESTCOMSPlus, later in
this section for information on how to activate the plugin. If the connection was successful,
BESTCOMSPlus will show Online in the lower right corner.

19.

Review settings or save a settings file if desired.

20.

Click the Disconnect button near the top of BESTCOMSPlus to close the RTD module connection.

Configure the BE1-11m to Communicate with the RTD Module

21.

Connect an Ethernet or USB cable between the PC and BE1-11m.

22.

Open the BE1-11 plugin in BESTCOMSPlus and connect to the BE1-11m.

23.

Use the Settings Explorer to open the Remote Module Communications screen under System
Parameters.

24.

Set the Status to Enabled. Set Communication Type to Ethernet or RS485. Set Remote Module ID
to match the remote module ID entered in Step 10.

25.

Perform this step if the RTD module is connected to the BE1-11m via RS-485. The RTD Module
communicates with the BE1-11m only at 19200 baud when using RS-485. Open the RS485 Setup
screen under Communications and set Baud Rate to 19200 Baud, Bits Per Character to 8 Bits,
Parity to No Parity, and Stop Bits to 1 stop bit.

26.

Use BESTCOMSPlus to send settings to the BE1-11m.

Procedure 2

The PC, BE1-11m, and RTD module are connected through a network. See Figure 321.

BE1-11m

RTD Module