Figure 395. Protection, Voltage, Undervoltage (27P-1) Screen

Undervoltage (27P-2) Starting

The 27P-2 protection element is set to trip when source voltage is too low for a successful start. The
motor manufacturer data indicates that the minimum voltage for a successful start is 85 percent of
nominal. The 27P-2 element is set to prohibit starting when voltage is below 85 percent of nominal. The
pickup setting is calculated in Equation 79.

π‘ƒπ‘–π‘π‘˜π‘’π‘ = 85% βˆ™ π‘π‘œπ‘šπ‘–π‘›π‘Žπ‘™ π‘‰π‘œπ‘™π‘‘π‘Žπ‘”π‘’ βˆ™

1

𝑃𝑇𝑅

= 0.85 βˆ™ 12,000 βˆ™

1

100

= 102 𝑉 π‘ π‘’π‘π‘œπ‘›π‘‘π‘Žπ‘Ÿπ‘¦

Equation 79. 27P-2 Pickup

Set a threshold to deactivate the element when there is no motor activity. The inhibit level is calculated in
Equation 80.

πΌπ‘›β„Žπ‘–π‘π‘–π‘‘ 𝐿𝑒𝑣𝑒𝑙 = 20% βˆ™ π‘π‘œπ‘šπ‘–π‘›π‘Žπ‘™ π‘‰π‘œπ‘™π‘‘π‘Žπ‘”π‘’ βˆ™

1

𝑃𝑇𝑅

= 0.20 βˆ™ 12,000 βˆ™

1

100

= 24 𝑉 π‘ π‘’π‘π‘œπ‘›π‘‘π‘Žπ‘Ÿπ‘¦

Equation 80. 27P-2 Inhibit Level

Select Three of Three mode, set the Pickup setting to 102 V, set the Inhibit Level to 24 V, and set the
Time Delay to 0 ms as shown in Figure 396.

Settings Calculation Examples