9424200996 Rev L

381

Reverse Tripping Direction (Overpower)

Pickup Setting Range = 1 to 6,000 Watts for 5A sensing

1 to 1,200 Watts for 1A sensing

Pickup Accuracy =

±3 or ±2 W, whichever is greater

Dropout should occur between 95-99% of the actual pickup value.

Step

Pickup Setting

Low

Actual Pickup

High

Low

*

Actual Dropout

High

* Pass/Fail

3

500 W

485 W

515 W

475 W

495 W

P / F

* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.

Forward Tripping Direction (Underpower)

Pickup Setting Range = 1 to 6,000 Watts for 5A sensing

1 to 1,200 Watts for 1A sensing

Pickup Accuracy =

±3 or ±2 W, whichever is greater

Reset should occur between 95-99% of the actual pickup value.

Step

Setting

Low

Pickup

High

Low

*

Dropout

High

*

Pass/Fail

3

500 W

485.0 W

515.0 W

475.0 W

495.0 W

P / F

5

250 W

242.5 W

257.5 W

237.5 W

247.5 W

P / F

5

50 W

48.5 W

51.5 W

47.5 W

49.5 W

P / F

* Reset range is calculated from the pickup setting and may need adjusted based on actual pickup.

Reverse Tripping Direction (Underpower)

Pickup Setting Range = 1 to 6,000 Watts for 5A sensing

1 to 1,200 Watts for 1A sensing

Pickup Accuracy =

±3 or ±2 W, whichever is greater

Reset should occur between 95-99% of the actual pickup value.

Step

Pickup Setting

Low

Actual Pickup

High

Low

*

Actual Dropout

High

* Pass/Fail

3

500 W

485 W

515 W

475 W

495 W

P / F

* Reset range is calculated from the pickup setting and may need adjusted based on actual pickup.