Table 40. Logic Inputs and Outputs

Name

Function

Purpose

Block

Input

Disables the 48 function when true

Trip

Output

True when the 48 element is in trip condition

Operational Settings

Incomplete sequence operational settings are configured on the Incomplete Sequence (48) settings
screen (Figure 72) in BESTCOMSPlus. Setting ranges and defaults are summarized in Table 41.

Figure 72. Incomplete Sequence Settings Screen

Table 41. Operational Settings

Setting

Range

Increment

Unit of Measure

Default

Mode

Disabled or Enabled

n/a

n/a

Disabled

Time Interval

0 to 7,200

0.01

seconds

0

Incomplete Sequence (48) Protection