Figure 396 – Basler Electric BE1-11m User Manual

Page 573

Advertising
background image

9424200996 Rev L

561

Figure 396. Protection, Voltage, Undervoltage (27P-2) Screen

Overvoltage (59P-1)

The 59-1 protection element is set to trip when source voltage is too large, and is especially important in a
synchronous motor. Because the motor is a constant kVA (power) device, the result of overvoltage is to
decrease the load current and the power factor if no additional excitation is added. In addition, newer
motors use less iron in the core and therefore the V/Hz ratio can cause air-gap flux saturation and
subsequent motor heating. The Pickup setting is calculated in Equation 81.

𝑃𝑖𝑐𝑘𝑢𝑝 = 110% ∙ 𝑁𝑜𝑚𝑖𝑛𝑎𝑙 𝑉𝑜𝑙𝑡𝑎𝑔𝑒 ∙

1

𝑃𝑇𝑅

= 1.10 ∙ 12,000 ∙

1

100

= 132 𝑉 𝑠𝑒𝑐𝑜𝑛𝑑𝑎𝑟𝑦

Equation 81. 59P-1 Pickup

Select Three of Three mode, set the Pickup setting to 132 V, and set the Time Delay to 1000 ms to avoid
tripping on spikes in the system. See Figure 397.

BE1-11m

Settings Calculation Examples

Advertising