Pickup verification (average restraint) – Basler Electric BE1-11m User Manual

Page 385

Advertising
background image

9424200996 Rev L

373

Step 5: Slowly increase the A-phase current in CT circuit 1 or 2 until OUT2 closes and record the

pickup. This should occur at 0.70 A

±0.05 A. Verify that there is an 87A target on the front-panel

display.

Step 6: Slowly decrease the A-phase current in CT circuit 1 or 2 until OUT2 reopens and record the

dropout. See the functional test report for acceptable ranges.

Step 7: Reset to the current levels in step 5 and reset all targets.

Step 8: Slowly decrease the A-phase current in CT circuit 1 or 2 until OUT2 closes and record the

pickup. This should occur at 0.30 A

±0.05 A. Verify that there is an 87A target on the front-panel

display.

Step 9: Slowly increase the A-phase current in CT circuit 1 or 2 until OUT2 reopens and record the

dropout. See the functional test report for acceptable ranges.

Step 10: To test the Restraint Slope 1 setting, connect two balanced three-phase current sources to the

BE1-11m in ABC rotation: 3.0

∠0°, 3.0∠–120°, 3.0∠120° amps to terminals D1 through D6 and

3.0

∠180°, 3.0∠60°, 3.0∠–60° amps to terminals F1 through F6 (1.5x tap).

Step 11: Slowly increase the A-phase current in CT circuit 1 or 2 until OUT2 closes and record the

pickup. This should occur at 3.75 A

±0.08 A. Verify that there is an 87A target on the front-panel

display.

Step 12: Reset to the current levels in step 9 and reset all targets.

Step 13: Slowly decrease the A-phase current in CT circuit 1 or 2 until OUT2 closes and record the

pickup. This should occur at 2.40 A

±0.05 A. Verify that there is an 87A target on the front-panel

display.

Step 14: To test the Restraint Slope 2 setting, connect two balanced three-phase current sources to the

BE1-11m in ABC rotation: 6.5

∠0°, 6.5∠–120°, 6.5∠120° amps to terminals D1 through D6 and

6.5

∠180°, 6.5∠60°, 6.5∠–60° amps to terminals F1 through F6 (3.25x tap).

Step 15: Slowly increase the A-phase current in CT circuit 1 or 2 until OUT2 closes and record the

pickup. This should occur at 8.83 A

±0.18 A. Verify that there is an 87A target on the front-panel

display.

Step 16: Reset to the current levels in step 12 and reset all targets.

Step 17: Slowly decrease the A-phase current in CT circuit 1 or 2 until OUT2 closes and record the

pickup. This should occur at 5.10 A

±0.10 A. Verify that there is an 87A target on the front-panel

display.

Step 18: (Optional.) Repeat steps 1 through 17 for the B-phase and C-phase current inputs.

Step 19: (Optional.) Repeat steps 1 through 18 for settings group 1, 2, and 3.

Pickup Verification (Average Restraint)

Step 1: Use BESTCOMSPlus to send the operational settings in Table 163. Reset all targets.

Table 163. Operational Settings (87R - Average)

Setting

Value

BESTCOMSPlus Screen

Description

Nominal
Phase Voltage

69.3 V

System Parameters, Motor
Configuration

Sets the nominal secondary
sensing voltage to 69.3 V

Nominal
Phase Current

5 A

System Parameters, Motor
Configuration

Sets the nominal secondary
sensing current to 5 amps

Nominal Aux.
Voltage

69.3 V

System Parameters, Motor
Configuration

Sets the nominal secondary
auxiliary voltage to 69.3 V

Phase CT 1
Ratio

1

System Parameters, Sensing
Transformers

Sets the phase CT ratio to 1

BE1-11m

Phase Current Differential (87) Test

Advertising