Basler Electric BE1-11m User Manual

Page 404

Advertising
background image

392

9424200996 Rev L

Setting

Value

BESTCOMSPlus Screen

Description

Full Load Amps

2

System Parameters, Motor
Configuration

Sets Full Load Amps to 3

Service Factor

1

System Parameters, Motor
Configuration

Sets Service Factor to 1

Element Mode

Standard
Curve

Protection, Thermal, Thermal
Curve (49TC)

Selects Standard Curve
mode

Standard Curve Time
Dial

10

Protection, Thermal, Thermal
Curve (49TC)

Sets Standard Curve Time
Dial to 10

K

0

Protection, Thermal, Thermal
Curve (49TC)

Sets K to 0

Overload

1

Protection, Thermal, Thermal
Curve (49TC)

Sets Overload pickup to 1

Max Emergency
Thermal Capacity

0

Protection, Thermal, Thermal
Curve (49TC)

Sets Max Emergency
Thermal Capacity to 0%

Running Cool Time
Constant

1

Protection, Thermal, Thermal
Curve (49TC)

Sets Running Cool Time
Constant to 1 minute

Stopped Cool Time
Constant

1

Protection, Thermal, Thermal
Curve (49TC)

Sets Stopped Cool Time
Constant to 1 minute

Hot Safe Stall Time

1

Protection, Thermal, Thermal
Curve (49TC)

Sets Hot Safe Stall Time to 1
second

Cold Safe Stall Time

1

Protection, Thermal, Thermal
Curve (49TC)

Sets Cold Safe Stall Time to
1 second

49TC

Enabled

Target Configuration, Targets

Enables 49TC target

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus Programmable Logic shown in Figure

267.

Figure 267. BESTlogicPlus Settings, Standard Curve

Step 3: Prepare to monitor the 49TC function operation. Operation can be verified by monitoring OUT1

(Tripped) and OUT2 (Overloaded). See Figure 267.

Step 4: Connect a three-phase 60 Hz current source to terminals D1 and D2 (IA), D3 and D4 (IB), and

D5 and D6 (IC).

Step 5: The following calculations are referenced in this test procedure.

The Overload Pickup Current is calculated in Equation 22.

𝐼

𝑑𝑝𝑒

= 𝑆 Γ— 𝑆𝐹 Γ— 𝐹𝐿𝐴 = 1 Γ— 1 Γ— 2 = 2 𝐴

Equation 22. Overload Pickup Current

Thermal Curve (49TC) Test

BE1-11m