59P - Phase Overvoltage Protection

Pickup
Setting Range ........................................................... 1 to 300 V
Accuracy....................................................................

±2% or ±1 V, whichever is greater

Dropout/Pickup Ratio ................................................ 98%

±1%

Timing Mode

Definite Timing

Setting Range ........................................................... 50 to 600,000 ms
Accuracy....................................................................

±1.5% or ±2 cycles, whichever is greater

Inverse Timing

Setting Range ........................................................... 0 to 9.9
Accuracy....................................................................

±8% or ±4 cycles, whichever is greater

Refer to the

Time Curve Characteristics

chapter

for information on available timing curves.

59X - Auxiliary Overvoltage Protection

Pickup
Setting Range ........................................................... 1 to 150 V
Accuracy....................................................................

±2% or ±1 V, whichever is greater

Dropout/Pickup Ratio ................................................ 98%

±1%

Timing Mode

Definite Timing

Setting Range ........................................................... 50 to 600,000 ms
Accuracy....................................................................

±1.5% or ±4 cycles, whichever is greater

Inverse Timing

Setting Range ........................................................... 0 to 9.9
Accuracy....................................................................

±8% or ±4 cycles, whichever is greater

Refer to the

Time Curve Characteristics

chapter

for information on available timing curves.

60FL - Fuse Loss

Time Delay ................................................................ Fixed at 50 ms

62 - Logic Timers

Modes ........................................................................ Pickup/Dropout, One-Shot/Non-Retriggerable,

One-Shot/Retriggerable, Oscillator, Integrating
Timer, Latched

Setting Range ........................................................... 0 to 9,999,000 ms
Accuracy....................................................................

±0.5% or ±12 ms, whichever is greater

66 - Starts per Time Interval Protection

Time Interval

Setting Range ........................................................... 1 to 1,440 min
Accuracy....................................................................

±0.5%

Number of Starts

Setting Range ........................................................... 1 to 100

Specifications - 25 Hz Operation