Functional test report, Restart delay, Time between starts – Basler Electric BE1-11m User Manual

Page 421

Advertising
background image

9424200996 Rev L

409

Step 15: Remove three-phase current. Verify that OUT1 (Starting) opens and OUT2 (Stopped) closes.

Step 16: Apply 10 Aac three-phase current. Verify that no start is possible and OUT2 (Stopped) and

OUT3 (Start Blocked) remain closed during the time between starts.

Step 17: Stop the timer when OUT4 (Start Blocked Removed) closes and record the time. The expected

timing is 60 seconds. Note that OUT3 (Start Blocked) opens when OUT4 (Start Blocked
Removed) closes.

Step 18: Apply 10 Aac three-phase current (simulate motor starting) and verify that a start is possible.

Remove three-phase current.

Functional Test Report

Restart Delay

Restart Delay Range = 0 to 7,200 min

Timing Accuracy =

±0.5% or ±3 cycles, whichever is greater

Step

Time Interval

Low

Actual Timing

High

Pass/Fail

8

60 s (1 min)

59.7 s

60.3 s

P / F

Time Between Starts

Time Between Starts Range = 0 to 7,200 min

Timing Accuracy =

±0.5% or ±3 cycles, whichever is greater

Step

Time Interval

Low

Actual Timing

High

Pass/Fail

17

60 s (1 min)

59.7 s

60.3 s

P / F

BE1-11m

Restart Inhibit Test