Name

Description

Symbol

Major Alarm

True when the Major Alarm is true. Refer to the

Alarms

chapter for more information.

Minor Alarm

True when the Minor Alarm is true. Refer to the

Alarms

chapter for more information.

Relay Trouble Alarm

True when a Relay Trouble alarm is active. Refer to the

Alarms

chapter for more information.

Targets

True when targets are active. Refer to the

Fault Reporting

chapter for more information.

Components

This group contains Logic Gates, Pickup and Dropout Timers, Latches, Logic Counters, and Comment
Blocks. Double-click or right-click on a gate to change the type. Table 82 lists the names and descriptions
of the objects in the Components group.

Table 82. Components Group, Names and Descriptions

Name

Description

Symbol

Logic Gates

AND

Input Output
0 0

0

0 1

0

1 0

0

1 1

1

NAND

Input Output
0 0

1

0 1

1

1 0

1

1 1

0

OR

Input Output
0 0

0

0 1

1

1 0

1

1 1

1

NOR

Input Output
0 0

1

0 1

0

1 0

0

1 1

0

XOR

Input Output
0 0

0

0 1

1

1 0

1

1 1

0

XNOR

Input Output
0 0

1

0 1

0

1 0

0

1 1

1

NOT
(INVERTER)

Input

Output

0

1

1

0