Phase current differential (87) test, Restrained functional test procedure, Pickup verification (maximum restraint) – Basler Electric BE1-11m User Manual

Page 383

Advertising
background image

9424200996 Rev L

371

Phase Current Differential (87) Test

Functional testing is a way to assess this protection system’s suitability for your application. Functional
testing goes beyond the more basic tests found in acceptance testing, but lacks the detailed function
testing that is part of the commissioning process.

Test each of the following functions to verify that this BE1-11m measures accurately, is within specified
tolerances, and operates correctly. These tests are also suitable for assisting in systematic
troubleshooting in the event that an operation is questioned. Revisiting the test of a specific function can
help verify whether the BE1-11m is operating within specified tolerances. For further assistance, contact
Basler Electric, Technical Sales Support.

Refer to the

Terminals and Connectors

chapter for terminal locations and connections.

Reset all targets prior to each test by navigating to the Metering > Status > Targets screen and pressing
the front-panel Reset key. Enter the appropriate username and password if prompted. Clear all logic prior
to each test by using the Settings Explorer in BESTCOMSPlus

® to open the BESTlogic™Plus

Programmable Logic screen and click the Clear button located on the toolbar. After new BESTlogicPlus
settings are made, click the Save button located on the toolbar to compile BESTlogicPlus. Upload
BESTlogicPlus settings by selecting Upload Logic to Device from the Communication pull-down menu.
Operational settings can be sent by selecting Upload Settings to Device from the Communication pull-
down menu or by clicking the Send Settings button on the toolbar.

The actual operating time of an output contact is equal to the recognition time plus the time delay setting
(accuracy) plus 6 milliseconds. Output contact operating time depends upon the type of test set used and
its operating characteristics.

A Functional Test Report is included at the end of this chapter. It should be used to record the results and
verify pickup and timing accuracy.

Refer to the

Phase Current Differential (87) Protection

chapter for more information on this function.

Restrained Functional Test Procedure

Pickup Verification (Maximum Restraint)

Step 1: Use BESTCOMSPlus to send the operational settings in Table 162. Reset all targets.

Table 162. Operational Settings (87R - Maximum)

Setting

Value

BESTCOMSPlus Screen

Description

Nominal
Phase
Voltage

69.3 V

System Parameters, Motor
Configuration

Sets the nominal secondary
sensing voltage to 69.3 V

Nominal
Phase Current

5 A

System Parameters, Motor
Configuration

Sets the nominal secondary
sensing current to 5 A

Nominal Aux.
Voltage

69.3 V

System Parameters, Motor
Configuration

Sets the nominal secondary
auxiliary voltage to 69.3 V

Phase CT 1
Ratio

1

System Parameters, Sensing
Transformers

Sets the phase CT 1 ratio to 1

Phase CT 2
Ratio

1

System Parameters, Sensing
Transformers

Sets the phase CT 2 ratio to 1

Phase VT
Ratio

1

System Parameters, Sensing
Transformers

Sets phase VT ratio to 1

Phase VT
Connection

4W-Y

System Parameters, Sensing
Transformers

Sets phase VT connection to
4W-Y

BE1-11m

Phase Current Differential (87) Test

Advertising