Display units, System units, Settings display modes – Basler Electric BE1-11m User Manual

Page 300

Advertising
background image

288

9424200996 Rev L

Setting

Range

Increment

Unit

Default

CT Source

*

CT1 or CT2

n/a

n/a

CT1

Phase VT Ratio

1 to 10,000

0.01

turns

ratio

1

Phase VT Connection

AB, BC, CA, AN, BN, CN, 3W-D,

or 4W-Y

n/a

n/a

4W-Y

27/59 Mode

PP or PN

n/a

n/a

PN

27R Mode

PP or PN

n/a

n/a

PN

Aux VT Ratio

1 to 10,000

0.01

turns

ratio

1

Aux VT Connection

AB, BC, CA, AN, BN, CN, or

Ground

n/a

n/a

AN

* For protection systems equipped with two sets of CTs.

Display Units

The Display Units screen is shown in Figure 240.

System Units

This setting configures the BE1-11m to display and report temperature in English or metric units of
measure.

Settings Display Modes

This setting defines how threshold settings are displayed in BESTCOMSPlus. Either primary units or
secondary units can be selected. The default setting is secondary units. The front panel displays
threshold settings in secondary units only.

Figure 240. Display Units Screen

Configuration

BE1-11m