Thermal curve (49tc), Standard curve – Basler Electric BE1-11m User Manual

Page 503

Advertising
background image

9424200996 Rev L

491

Thermal Curve (49TC)

The Standard and IEC curves are defined below.

Standard Curve

The Standard Curve Time Dial setting determines the time to trip when the 49TC element is configured
for Standard Curve mode. The standard curve provides a

I

eq

2

curve with a range of time dial settings that

accommodate a wide range of motor timings. The standard curve equation is shown in Equation 35.

t = TD × 88.744132 × ln

⎡ �

I

eq

S ∙ SF ∙ FLA�

2

I

eq

S ∙ SF ∙ FLA�

2

− 1⎦⎥

With max value of

I

eq

/(S

•SF•FLA) of 10.

Equation 35. Standard Curve

Where:

t

= Operating time

I

eq

= Measured equivalent motor current

TD = Time Dial

FLA = Full Load Amps

SF = Service Factor

S

= Overload Scaler

ln

= Natural log

BE1-11m

Time Curve Characteristics