Negative-sequence voltage (47) protection – Basler Electric BE1-11m User Manual

Page 51

Advertising
background image

9424200996 Rev L

39

Negative-Sequence Voltage (47)
Protection

Negative-sequence voltage protection is included as a mode of the 59X (Auxiliary Overvoltage) element.
Refer to the

Auxiliary Overvoltage (59X) Protection

chapter for information on how to set up and program

the V2 (negative-sequence voltage) mode of the 59X element.

Negative-sequence voltage protection is used to sense power-system imbalance. This situation occurs
when a large single-phase load is switched onto the system, or when transformer-input fuses blow in only
one or two phases. Negative-sequence voltage protection is good for detecting improper phasing when
an oncoming generator is paralleled to the power system. All motor loads should be protected from the
heating caused by unbalanced voltage (either on the bus or on each motor feeder). Industry standards
state that the existence of unbalanced voltage feed results in 4 to 10 times the current imbalance. For a
motor feeder, the negative-sequence voltage unbalances should not exceed 5 percent to avoid
overheating and damage.

BE1-11m

Negative-Sequence Voltage (47) Protection

Advertising