Figure 352. Protection, Current, Instantaneous Overcurrent (50-1) Screen

Instantaneous Overcurrent (50-2) - Ground Fault Protection

The system is solidly grounded so that a ground fault draws current in the magnitude of a three-phase
fault per IEEE C37.96-2000, IEEE Guide for AC Motor Protection. To determine the three-phase fault
current, consider that the motor subtransient reactance of 0.15 is the limiting impedance. The pickup
setting is calculated using Equation 44. A pickup setting of 1/3 of the instantaneous three-phase fault
current is recommended per IEEE C37.96-2000, IEEE Guide for AC Motor Protection.

π‘ƒπ‘–π‘π‘˜π‘’π‘ = οΏ½

1

𝑋"𝑑

βˆ™

𝐹𝐿𝐴

𝐢𝑇 π‘…π‘Žπ‘‘π‘–π‘œ

οΏ½ βˆ™

1
3

= οΏ½

1

0.15

βˆ™

363

80

οΏ½ βˆ™

1
3

= 10.08 𝐴 π‘ π‘’π‘π‘œπ‘›π‘‘π‘Žπ‘Ÿπ‘¦

Equation 44. 50-2 Pickup

Select 3I0 (residual) mode and set the Pickup setting to 10.08 A as shown in Figure 353.

Figure 353. Protection, Current, Instantaneous Overcurrent (50-2) Screen

Instantaneous Overcurrent (50-3) - Unbalance Protection

The NEMA MG-1 standard states that the existence of unbalanced voltage feed results in four to 10 times
the current imbalance. The negative-sequence voltage unbalances should not exceed 5 percent. This
application uses negative-sequence current as the input to an overcurrent element to sense unbalance
conditions. For conservative protection, choose 4

β€’ 5%, which is 20 percent imbalance. A 10 second

delay is appropriate because the heating is slow (motor mass is large). The pickup setting calculation is
shown in Equation 45.

π‘ƒπ‘–π‘π‘˜π‘’π‘ = π‘π‘’π‘šπ‘Ž π‘†π‘‘π‘Žπ‘›π‘‘π‘Žπ‘Ÿπ‘‘ (5%) βˆ™ πΆπ‘œπ‘›π‘ π‘’π‘Ÿπ‘£π‘Žπ‘‘π‘–π‘£π‘’ π‘ƒπ‘Ÿπ‘œπ‘‘π‘’π‘π‘‘π‘–π‘œπ‘› (4) βˆ™ 𝐹𝐿𝐴

π‘†π‘’π‘π‘œπ‘›π‘‘π‘Žπ‘Ÿπ‘¦

= 0.05 βˆ™ 4 βˆ™ 4.54 = 0.908 𝐴 π‘ π‘’π‘π‘œπ‘›π‘‘π‘Žπ‘Ÿπ‘¦

Equation 45. 50-3 Pickup

Select I2 mode, set the Pickup setting to 0.908 A, and set the Time Delay to 10 seconds as shown in
Figure 354.

BE1-11m

Settings Calculation Examples