Basler Electric BE1-11m User Manual

Page 384

Advertising
background image

372

9424200996 Rev L

Setting

Value

BESTCOMSPlus Screen

Description

27/59 Mode

PN

System Parameters, Sensing
Transformers

Sets 27/59 mode to phase-
neutral

Circuit 1 Tap

2.00

System Parameters, Sensing
Transformers

Sets the tap for circuit 1 to
2.00 A secondary

Circuit 2 Tap

2.00

System Parameters, Sensing
Transformers

Sets the tap for circuit 2 to
2.00 A secondary

Mode

Phase
Differential

Protection, Current, Phase
Differential (87)

Sets the type of operation
protection to traditional phase
current differential

Slope Mode

Maximum

Protection, Current, Phase
Differential (87)

Sets the element to operate
using maximum restraint
current

Min. Rest.
Pickup (MOT)

0.10

Protection, Current, Phase
Differential (87)

Sets the minimum amount of
operate current required for a
trip to 0.10x tap

Restraint
Slope 1 (%)

20

Protection, Current, Phase
Differential (87)

Sets the 1

st

slope of the

restraint characteristic to 20%

2

nd

Slope

Pickup (MOT)

3.00

Protection, Current, Phase
Differential (87)

The 2

nd

slope is active when

the measured maximum
restraint current is greater 3x
tap

Restraint
Slope 2 (%)

40

Protection, Current, Phase
Differential (87)

Sets the 2

nd

slope of the

restraint characteristic to 40%

Time Delay
(ms)

100

Protection, Current, Phase
Differential (87)

Sets the trip time delay to 100
ms

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 263.

Blocking is disabled.

OUT1 closes for 87 Trip.

OUT2 closes for 87 Pickup.

Fault recording is enabled.

Figure 263. BESTlogicPlus Settings (87R)

Step 3: Prepare to monitor the 87R function operation. Operation can be verified by monitoring OUT2

(see Figure 263).

Step 4: To test the Minimum Restrained Pickup setting, connect two balanced three-phase current

sources to the BE1-11m in ABC rotation: 0.5

∠0°, 0.5∠–120°, 0.5∠120° amps to terminals D1

through D6 and 0.5

∠180°, 0.5∠60°, 0.5∠–60° amps to terminals F1 through F6 (0.25x tap).

Phase Current Differential (87) Test

BE1-11m