Programmable Inputs - Remote RTD

RTD Type Selection

This settings example uses nine RTDs that are all 100

Ω, platinum. Open the Programmable Inputs,

Remote RTD, RTD Type Selection screen shown in Figure 345. Select 100-

Ω platinum construction for

RTD#1 through RTD#9. Select Disabled for RTD#10 through RTD#12.

Figure 345. Programmable Inputs, Remote RTD, RTD Type Selection Screen

RTD Block Configuration

For this example, the RTDs are configured into three configuration blocks. Six of the RTDs are used for
stator thermal measurements, two are used for bearing measurements, and one is used for ambient
temperature.

Navigate to Programmable Inputs, Remote RTD, RTD Block Configuration and set RTD Configuration
Blocks 1-3 as shown in Figure 346.