Timing verification (3i0 mode) – Basler Electric BE1-11m User Manual

Page 371

Advertising
background image

9424200996 Rev L

359

Step 8: (Optional.) Repeat steps 1 through 7 for settings group 1, 2, and 3.

Step 9: (Optional.) Repeat steps 1 through 8 for 51-2, 51-3, 51-4, and 51-5.

Step 10: (Optional.) Repeat steps 1 through 9 with CT Circuit 2 as the source for protection systems

equipped with two sets of CTs. In step 5, replace D1 with F1, D2 with F2, etc.

Timing Verification (3I0 Mode)

Step 1: Use BESTCOMSPlus to open the Protection, Current, Inverse Overcurrent (51-1) screen and

send the test settings in Table 152 to the BE1-11m for settings group 0.

Table 152. Timing Test Settings (3I0 Mode)

Pickup Setting

Time Curve

0.5 A (5 A sensing), 0.1 A (1 A sensing)

I2

Step 2: Prepare to monitor the 51-1 timings. Timing accuracy is verified by measuring the elapsed time

between a sensing current change and OUT1 closing.

Step 3: Connect a current source to BE1-11m terminals D1 and D2 (A-phase).

Step 4: Using the values listed in Table 153, apply the appropriate current values, and measure the

time between the application of current and the closure of OUT1. Record the results.

Step 5: Repeat step 4 for all of the current and time dial settings for your current sensing type.

Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3.

Step 7: (Optional.) Repeat steps 1 through 6 for 51-2, 51-3, 51-4, and 51-5.

Step 8: (Optional.) Repeat steps 1 through 7 with CT Circuit 2 as the source for protection systems

equipped with two sets of CTs. In step 3, replace D1 with F1, D2 with F2, etc.

Table 153. Timing Test Settings (3I0 Mode)

Sensing Type

Time Dial

Applied Current

5 A

0.5

1.00 A

2.50 A

12.50 A

5.0

1.00 A

2.50 A

12.50 A

9.9

1.00 A

2.50 A

12.50 A

1 A

0.5

0.20 A

0.50 A

2.50 A

5.0

0.20 A

0.50 A

2.50 A

9.9

0.20 A

0.50 A

2.50 A

BE1-11m

Inverse Overcurrent (51) Test

Advertising