9424200996 Rev L

41

Phase Overvoltage (59P) Protection

Two phase overvoltage (59P) elements monitor the sensing voltage applied to the BE1-11m. An element
can be configured to protect against overvoltage when the phase voltage increases above a defined level.

The two, identical overvoltage protection elements are designated 59P-1 and 59P-2. Element logic
connections are made on the BESTlogic

Plus screen in BESTCOMSPlus® and element operational

settings are configured on the Overvoltage settings screen in BESTCOMSPlus. A summary of the logic
inputs and outputs and operational settings appears at the end of this chapter.

BESTCOMSPlus Navigation Path: Settings Explorer, Protection, Voltage, Overvoltage (59P)

HMI Navigation Path: Settings Explorer, Protection, Settings Group x (where x = 0 to 3), Voltage
Protection, Overvoltage 59P

Element Operation

Overvoltage protection can be used to prevent large transformer and equipment damage when an
overvoltage condition exists. For example, an overvoltage condition could occur when the tap changing
control fails.

Modes of Protection

Three modes of protection are available. The One of Three mode activates protection when one of the
three phases of voltage increases above the Pickup setting. The Two of Three mode activates protection
when any two of the three phases of voltage increases above the Pickup setting. The Three of Three
mode activates protection when all three phases of voltage increase above the Pickup setting.

Voltage Response

The overvoltage element can be set to monitor VPP or VPN. This is determined by the 27/59 Mode
parameter of the phase VT connections found on the System Parameters/Sensing Transformers settings
screen in BESTCOMSPlus. For more information on the VTP setup for PP or PN voltage response, see
the

Configuration

chapter.

Timings

The timing mode can be set for definite or inverse. For details on the inverse time curve, refer to the

Time

Curve Characteristics

chapter.

Pickup and Trip

The Pickup output occurs first, followed by the Trip output.

Pickup

The Pickup output becomes true when the measured voltage increases above the voltage threshold
established by the Pickup setting. In BESTlogicPlus, the Pickup output can be connected to other logic
elements to annunciate the condition, control other elements in logic, and start the fault recorder (logic
element FAULTTRIG).

Assertion of the Pickup output initiates a timer that begins timing to a trip. The duration of the timer is
established by the Time Delay (definite timing) or Time Dial (inverse timing). A Time Delay or Time Dial
setting of zero (0) makes the 59P element instantaneous with no intentional time delay.

Trip

The Trip output becomes true if an overvoltage pickup condition persists for the duration of the element
Time Delay setting or calculated inverse time. In BESTlogicPlus, the Trip output can be connected to
other logic elements and to a physical relay output to annunciate the condition and to initiate corrective

BE1-11m

Phase Overvoltage (59P) Protection