background image

142

9424200996 Rev L

Figure 105. Analog Metering, Differential Screen

Energy

Energy is metered for positive and negative watthours and varhours. Watthour and varhour values are
calculated per minute as shown in Equation 15.

Primary VT Ratio × Primary CT Ratio

60 minutes

× Secondary Watts or Vars

Equation 15. Energy Data Equation

Watt and var values are updated every 250 milliseconds and watthour and varhour values are logged
once every minute. Energy registers are stored in nonvolatile memory at 15-minute intervals.

Watthour values and varhour values can be read, reset, or changed through the front panel or
communication ports. A lagging power factor load will report positive watts and positive vars.

Energy metering data is found in BESTCOMSPlus (Figure 106) and on the Metering > Analog Metering >
Energy screen of the front-panel display.

Figure 106. Analog Metering, Energy Screen

Metering