Pulse mode, Functional test report – Basler Electric BE1-11m User Manual

Page 425

Advertising
background image

9424200996 Rev L

413

Step 3: Use the Metering Explorer of BESTCOMSPlus to open the Control, Virtual Switches tree branch

(Figure 275). Using select-before-operate, perform the following steps to control a virtual switch.

Step 5: Click the 43-1 button to select it. Login may be required. The On or Off indicator (current state)

will begin to flash.

Note

If step 6 is not performed within 25 seconds of step 5, the indicator will
stop flashing and the 43-1 button will have to be re-selected.

Step 6: Click on the 43-1 button a second time to operate it. After clicking Yes, the On or Off indicator

(previous state) will stop flashing and the On or Off indicator (current/new state) will light.

Step 7: Verify that OUT1 contact closes and remains closed.

Step 8: Repeat steps 5 and 6 to change the state of the 43-1 switch to OFF. Verify that OUT1 contact

opens and remains open.

Step 9: (Optional.) Repeat steps 1 through 8 for 43-2, 43-3, 43-4, and 43-5.

Step 10: (Optional.) Repeat steps 1 through 9 for settings group 1, 2, and 3.

Pulse Mode

Step 1: Use BESTCOMSPlus to change the 43-1 element mode to Pulse.

Step 2: Prepare to monitor the virtual switch operation. An ohmmeter or continuity tester can be used to

monitor the contact status of OUT1.

Step 3: Using the front-panel display, navigate to Metering > Control > Virtual Switches. Highlight the

first switch (43-1) and press the Right key on the front panel to enter the 43-1 control screen.
Use the Edit key to login. Highlight Operate and then press the Edit key to change the state of
the 43-1. Using the Up/Down keys select PUL and then press the Edit key. Verify that OUT1
contact closes for 200 milliseconds and returns to the open state.

Step 4: (Optional.) Repeat steps 1 through 3 for 43-2, 43-3, 43-4, and 43-5.

Step 5: (Optional.) Repeat steps 1 through 4 for settings group 1, 2, and 3.

Functional Test Report

Function

Pass/Fail

Switch/Pulse Mode

P / F

Switch Mode

P / F

Pulse Mode

P / F

BE1-11m

Virtual Control Switches (43) Test