72

9424200996 Rev L

Element Blocking

Fuse Loss

The fuse loss element (60FL) can also be set to supervise the 51/27R function. It is possible to set the
60FL element to automatically prevent misoperation on loss of sensing voltage. When the 51/27R
function is set for control and a 60FL condition is detected, the inverse overcurrent elements will be
disabled. When the 51/27R function is set for restraint and a 60FL condition is detected, the inverse
overcurrent elements will remain enabled but the pickup will not be adjusted from 100% of its setting. See
the

Fuse Loss (60FL)

chapter for more information.

Protective elements blocked by 60FL should be set so that trip times are 60 milliseconds or greater to
assure proper coordination of blocking.

Block Logic Input

The Block input provides logic-supervision control of the element. When true, the Block input disables the
element by forcing the Trip and Pickup outputs to logic 0 and resetting the element timer. Connect the
element Block input to the desired logic in BESTlogicPlus. When the element is initially selected from the
Elements view, the default condition of the Block input is a logic 0.

Logic Connections

Inverse overcurrent element logic connections are made on the BESTlogicPlus screen in
BESTCOMSPlus. The inverse overcurrent element logic block is illustrated in Figure 50. Logic inputs and
outputs are summarized in Table 25.

Figure 50. Inverse Overcurrent Element Logic Block

Table 25. Logic Inputs and Outputs

Name

Logic Function

Purpose

Block

Input

Disables the 51 function when true

Trip

Output

True when the 51 element is in a trip condition

Pickup

Output

True when the 51 element is in a pickup condition

Operational Settings

Inverse overcurrent element operational settings are configured on the Inverse Overcurrent (51) settings
screen (Figure 51) in BESTCOMSPlus. Setting ranges and defaults are summarized in Table 26.

Inverse Overcurrent (51) Protection

BE1-11m