The BE1-11m monitors internal systems, external interfaces, and power system equipment and
annunciates an alarm when one of these components fail. An alarm can be configured as latching or non-
latching with a status of major or minor. It can also be used as an input to other logic blocks in
BESTlogic

Plus. Latching alarms are stored in nonvolatile memory and are retained even when BE1-11m

operating power is lost. Active alarms are displayed on the front-panel display, web page interface, and
through BESTCOMSPlus

® until they are cleared. Non-latching alarms are cleared when BE1-11m

operating power is lost.

If an alarm is configured as Major, a front-panel Major Alarm LED lights when the alarm is active. The
front-panel Minor Alarm LED operates in a similar manner. Each alarm provides a logic output that can be
connected to a physical output or other logic input using BESTlogicPlus Programmable Logic.

The ability to program the reporting and display of alarms along with the automatic display priority feature
of the front-panel display gives the BE1-11m the functionality of a local and remote alarm annunciator.
See the

Controls and Indicators

chapter for more information on the automatic display priority logic.

A detailed list of alarms is provided in Table 63.

Table 63. Available Alarms

Name

Description

101 Blocking Tag Status

101 breaker control switch block tag is set

3I0 Demand

Neutral current unbalance demand

43-1 Blocking Tag Status

43-1 virtual switch block tag set

43-2 Blocking Tag Status

43-2 virtual switch block tag set

43-3 Blocking Tag Status

43-3 virtual switch block tag set

43-4 Blocking Tag Status

43-4 virtual switch block tag set

43-5 Blocking Tag Status

43-5 virtual switch block tag set

87 Alarm

Current Differential

Analog

Analog-to-digital converter error

Breaker Fail

Breaker failure

Breaker Monitor 1

Breaker alarm 1 threshold exceeded

Breaker Monitor 2

Breaker alarm 2 threshold exceeded

Breaker Monitor 3

Breaker alarm 3 threshold exceeded

Changes Lost

Password access lost. Read only

Date Time Set

The date/time was set by the user

Defaults Cal Loaded

Remote Module 1 or 2 Alarm

Defaults Loaded

Remote Module 1 or 2 Alarm

DNP Polls Error

DNP polling failure

Ethernet Excess Traffic

Local network overloaded

Ethernet Link Lost

Ethernet communication lost

Fault Report Timeout

True if fault event trigger lasts longer than 60 seconds

Firmware Change

Firmware has been changed

Flash Failure

Remote Module 1 or 2 Alarm

Freq Out Of Range

Frequency is out of range

Fuse Loss

One or more phases of voltage lost