Timing verification (standard curve) – Basler Electric BE1-11m User Manual

Page 411

Advertising
background image

9424200996 Rev L

399

Timing Verification (Standard Curve)

Time Dial Range = 1 to 20

Timing Accuracy =

±5% or ±2½ cycles, whichever is greater

Step

Time Dial

Applied Current

Low

Actual Timing

High

Pass/Fail

7

10

10 A

34.409 sec

38.031 sec

P / F

11

10

10 A

30.276 sec

33.463 sec

P / F

Timing Verification (Standard Curve with Emergency Start)

Time Dial Range = 1 to 20

Timing Accuracy =

±5% or ±2½ cycles, whichever is greater

Step

Time Dial

Applied Current

Low

Actual Timing

High

Pass/Fail

17

10

10 A

68.818 sec

76.062 sec

P / F

Timing Verification (Standard Curve with RTD Biasing)

Time Dial Range = 1 to 20

Timing Accuracy =

±5% or ±2½ cycles, whichever is greater

Step

Time Dial

Applied Current

Low

Actual Timing

High

Pass/Fail

22

10

10 A

29.934 sec

33.085 sec

P / F

BE1-11m

Thermal Curve (49TC) Test