Timing Verification

Time Delay Range = 0 ms or 50 to 600,000 ms

Timing Accuracy =

±0.5% or ±2 cycles, whichever is greater

Step

Time Delay Setting

Low

Actual Timing

High

Pass/Fail

4

60,000 ms

59,700 ms

60,300 ms

P / F

5

0 ms

0 ms

34 ms

P / F

5

50 ms

17 ms

84 ms

P / F

Power Factor (55) Test