268

9424200996 Rev L

2.

Enter the username and password of the administrator and then click the Log In button. The default
Administrator username is “A” and the default Password is “A”.

3.

Only an administrator can modify usernames and passwords on the Username Setup screen (Figure
226)
. Usernames and passwords can be as many as 16 alphanumeric characters in length and are
not case sensitive.

Figure 226. Username Setup Screen

4.

In the left-hand column, highlight any username labeled NOT ASSIGNED or highlight a specific
username to change it.

5.

On the right side of the screen, enter a username.

6.

Enter a password for the user.

7.

Re-enter the password to verify it.

8.

Using Table 88 as a reference, enter the maximum access level allowed for the user.

9.

Enter the number of days to expiration of the password or leave at default (0) for no expiration.

10.

Click the Save User button to save to the settings to BESTCOMSPlus memory.

11.

Pull down the Communication menu and select Upload Security to Device. The Login dialog box pops
up. An administrator level is required to upload security settings to the device.

12.

Enter the username and password of the administrator and then click the Log In button. The default
administrator username is “A” and the default password is “A”. BESTCOMSPlus notifies you when
the upload is successful.

Port Access Setup

1.

Use the Settings Explorer in BESTCOMSPlus to select Port Access Setup under General Settings,
Device Security Setup. The Port List screen is shown in Figure 227.

Figure 227. Port List Screen