System parameters - sensing transformers – Basler Electric BE1-11m User Manual

Page 554

Advertising
background image

542

9424200996 Rev L

Figure 370. General Settings, Display Units Screen

Style Number

The BE1-11m style number shown in Figure 371 is used in this application example. The style number is
defined below.

Figure 371. BE1-11 Style Number

M ......... Application Option ...................... Motor

6 .......... Phase CT Option ........................ CT1 - 5 Amp Nominal / CT2 - 5 Amp Nominal

D .......... Ground CT Option ...................... CT1 - 5 Amp Nominal / CT2 - 5 Amp Nominal

2 .......... Power Supply Option ................. 125/250 Vac/dc

M ......... RS-485 Port Protocol ................. Modbus

1 .......... Ethernet Protocol ....................... BESTnetPlus Only

J .......... Case Option ............................... Vertical Case

2 .......... Alarm Contact Option ................. Normally Closed (closes upon power removal / watchdog failure)

P .......... Option 1 ...................................... Phase Differential

0 .......... Network Connections ................. Copper

E .......... Language ................................... English

0 .......... Option 2 ...................................... None

00 ........ Firmware Option ......................... Latest Release

System Parameters - Sensing Transformers

Phase CT Ratios

The motor manufacturer data for full-load amps (FLA) is 205 A under normal running conditions. Select
phase CTs so that the FLA is 50 percent or greater of the rated phase CT primary current. To minimize
CT saturation, select the phase CT primary current so the FLA is 100 percent of the phase CT primary or
slightly less, never more. IEEE states that “CT saturation is minimized by keeping burdens low (especially
the dc resistive component), by using high-ratio current transformers, and by selecting current
transformers with a high knee-point (saturation) voltage.” (IEEE Std C37.96-2000, IEEE Guide for AC
Motor Protection
).

Select CTs with a primary rating of 300 A; then the ratio with 5A CTs used in this application example is
60 (300:5). The secondary current measured by the BE1-11m is 3.41 A (205 A ÷ 60) when the motor is at
full load. CTs with an accuracy class of C100 and greater provide a satisfactory knee-point voltage for the

Settings Calculation Examples