Alarm settings, User programmable alarms – Basler Electric BE1-11m User Manual

Page 177

Advertising
background image

9424200996 Rev L

165

Name

Description

Setting Change

Setting change made by user

Settings Group 0

Setting group 0 is active

Settings Group 1

Setting group 1 is active

Settings Group 2

Setting group 2 is active

Settings Group 3

Setting group 3 is active

SGC Active

Active setting group changed

SGC Logic Override

Setting group control was overridden by logic

Trip Coil Monitor

Monitored trip circuit open

uP Reset Alarm

Microprocessor watchdog circuit timed out

Var Negative Demand

Negative var demand maximum exceeded

Var Positive Demand

Positive var demand maximum exceeded

Watt Forward Demand

Forward watt demand maximum exceeded

Watt Reverse Demand

Reverse watt demand maximum exceeded

Alarm Settings

BESTCOMSPlus Navigation Path: Settings Explorer, Alarm Configuration, Alarms

HMI Navigation Path: Not available through the front panel

Alarms are enabled using BESTCOMSPlus. Use the Settings Explorer to open the Alarm Configuration,
Alarms tree branch. Configure alarms by selecting Disabled, Latching, or Non-Latching from the Minor,
Major, and Logic drop-down menus next to the alarms. Refer to Figure 129.

Figure 129. Alarm Settings Screen

User Programmable Alarms

BESTCOMSPlus Navigation Path: Settings Explorer, Alarm Configuration, User Programmable Alarms

HMI Navigation Path: Not available through the front panel

Sixteen user programmable alarms are available. BESTlogicPlus Programmable Logic is used to set up
alarm logic. User alarm labels are programmed on the User Programmable Alarms screen (Figure 130)

BE1-11m

Alarms

Advertising