At this point, the logic variable will change from an energized (logic 1 or true) state to a de-energized
(logic 0 or false) state.

Figure 25. Digital Input Conditioning Timing Diagram

Setting the Contact Inputs

BESTCOMSPlus Navigation Path: Settings Explorer, Programmable Inputs, Contact Inputs

HMI Navigation Path: Settings Explorer, Contact Inputs

Settings and labels for the contact inputs are set using BESTCOMSPlus

®.

Each of the seven inputs has two settings and three labels. The settings are Recognition Time and
Debounce Time. The labels include a label to describe the input, a label to describe the Energized State,
and a label to describe the De-Energized State. Labels are used by the BE1-11m's reporting functions.

To edit the settings or labels, use the Settings Explorer to open the Programmable Inputs, Contact Inputs
tree branch as shown in Figure 26.

Figure 26. Contact Inputs Screen

BE1-11m

Contact Inputs and Outputs