Breaker Operate Time Monitoring

The breaker operate time monitor tracks the time from when a trip output occurs (defined by the Trip logic
expression) to when the fast current detector observes that current is zero in all three breaker poles. This
time is reported as a line in the fault summary reports. See the

Fault Reporting

chapter for more

information about the Trip logic expression and fault summary reports.

Breaker operate time can be monitored to give an alarm when the value exceeds a threshold. Breaker
Alarms
provides more information about this feature.

Breaker Alarms

Three alarm points are included in the programmable alarms for checking breaker monitoring functions.
Each alarm point can be programmed to monitor any of the three breaker monitoring functions, operations
counter, interruption duty, or clearing time. An alarm threshold can be programmed to monitor each
function. Alternately, three different thresholds can be programmed to monitor one of the monitored
functions.

Breaker Alarms Settings

BESTCOMSPlus Navigation Path: Settings Explorer, Alarm Configuration, Breaker Monitoring

HMI Navigation Path: Settings Explorer, Alarm Configuration, Breaker Monitor

Settings are made using BESTCOMSPlus. Use the Settings Explorer to open the Alarm Configuration,
Breaker Monitoring tree branch shown in Figure 136.

Using the pull-down menus and settings boxes, make the application-appropriate settings to the breaker
alarms.

Table 67 summarizes the breaker alarms settings.

Table 67. Breaker Alarms Settings

Setting

Range/Unit of Measure/Increment

Default

Mode

Disabled, Duty, Operation, or Clearing Time

Disabled

Threshold

Duty

0 to 200 percent, increment = 1

0

Operation

0 to 99,999 breaker operations, increment = 1

0

Clearing Time

0 to 1,000 milliseconds, increment = 1

0

Breaker Monitoring