Figure 349. Protection, Thermal, RTD Bias Curve Screen

Set the Center RTD Bias Temperature (point 2) to the motor hot running temperature. Recall from the
motor manufacturer data that the insulation is class F and the manufacturer allows an 80

Β°C stator

temperature rise. Allow for a 10 percent overage for hot spots. Refer to the Center RTD Bias Temperature
Equation 41.

πΆπ‘’π‘›π‘‘π‘’π‘Ÿ 𝑅𝑇𝐷 π΅π‘–π‘Žπ‘  π‘‡π‘’π‘šπ‘π‘’π‘Ÿπ‘Žπ‘‘π‘’π‘Ÿπ‘’ = οΏ½π‘‡π‘’π‘šπ‘π‘’π‘Ÿπ‘Žπ‘‘π‘’π‘Ÿπ‘’

𝑅𝑖𝑠𝑒 π‘œπ‘“ π‘†π‘‘π‘Žπ‘‘π‘œπ‘Ÿ

βˆ™ 10% π‘œπ‘£π‘’π‘Ÿπ‘Žπ‘”π‘’οΏ½ + π΄π‘šπ‘π‘–π‘’π‘›π‘‘ π‘‡π‘’π‘šπ‘π‘’π‘Ÿπ‘Žπ‘‘π‘’π‘Ÿπ‘’

= (80°𝐢 βˆ™ 1.10) + 40°𝐢

= 88°𝐢 + 40°𝐢 = 128°𝐢

Equation 41. Center RTD Bias Temperature

A good starting point for the center point Thermal Capacity (%TC) is the percentage difference between
the Hot Safe Stall Time and the Cold Safe Stall Time. This point can be modified later after observation
and motor monitoring. The initial calculation for %TC is given in Equation 42.

%𝑇𝐢 = 100% οΏ½1 βˆ’

π»π‘œπ‘‘ π‘†π‘Žπ‘“π‘’ π‘†π‘‘π‘Žπ‘™π‘™ π‘‡π‘–π‘šπ‘’

πΆπ‘œπ‘™π‘‘ π‘†π‘Žπ‘“π‘’ π‘†π‘‘π‘Žπ‘™π‘™ π‘‡π‘–π‘šπ‘’

οΏ½

= 100% οΏ½1 βˆ’

9

10οΏ½ = 10 %𝑇𝐢

Equation 42. Center Point Thermal Capacity

Set the Center RTD Bias Temperature (point 2) to 128

Β°C and 10 percent thermal capacity per the results

from Equation 41 and Equation 42.

The Maximum RTD Bias Temperature (point 3) is set to 155

Β°C and 100 percent thermal capacity. These

values are determined by the maximum insulation factor of F according to the motor manufacturer data.

Resistance Temperature Detector (49RTD)

The RTDs can be used as a direct source for protection as well. The maximum stator winding insulation
temperature is 155

Β°C per the motor manufacturer data.

Set the 49RTD-1 protection element as shown in Figure 350 to protect the stator winding insulation.
Voting is set to 2, meaning at least 2 RTDs must be at 155

Β°C or higher to result in a trip. A delay is not

required for the reason that temperatures change slowly because of the large motor thermal mass.