Energy data reporting, 27p - phase undervoltage protection, 32 - power protection – Basler Electric BE1-11m User Manual

Page 448

Advertising
background image

436

9424200996 Rev L

Reactive Power
5 Ampere CT Range ................................................. –7,500 var to +7,500 var
1 Ampere CT Range ................................................. –1,500 var to +1,500 var
Accuracy....................................................................

±1% at zero power factor

Energy Data Reporting

5 Ampere CT Range ................................................. 1,000 GWh or 1,000 Gvarh
1 Ampere CT Range ................................................. 1,000 GWh or 1,000 Gvarh
Units of Measure ....................................................... kilo
Rollover Value of Registers....................................... 1,000,000,000 kWhr or kvarhr
Accuracy....................................................................

±1% at unity power factor

27P - Phase Undervoltage Protection

Pickup
Setting Range ........................................................... 1 to 300 V
Accuracy....................................................................

±2% or ±1 V, whichever is greater

Reset/Pickup Ratio .................................................... 102%

±1%

Inhibit Level
Setting Range ........................................................... 1 to 300 V
Accuracy....................................................................

±2% or ±1 V, whichever is greater

Reset/Inhibit Ratio ..................................................... 102%

±1%

Timing Mode

Definite Timing

Setting Range ........................................................... 50 to 600,000 ms
Accuracy....................................................................

±0.5% or ±2 cycles, whichever is greater

Inverse Timing

Setting Range ........................................................... 0 to 9.9
Accuracy....................................................................

±5% or ±2 cycles, whichever is greater
Refer to the

Time Curve Characteristics

chapter for

information on available timing curves.

32 - Power Protection

Pickup
5 Ampere CT Setting Range ..................................... 1 to 6,000 W, three-phase
1 Ampere CT Setting Range ..................................... 1 to 1,200 W, three-phase
Accuracy....................................................................

±3% of setting or ±2 watts, whichever is greater,

at unity power factor. (Accuracy of phase
relationship measurement between V and I is
accurate to within 0.5 degrees when I is greater
than 0.1 Aac and V is greater than 5 Vac. The
power and var measurements at power factor
other than 1.0 are affected accordingly.)

Dropout ...................................................................... 95 to 99% of the actual pickup value

Time Delay
Setting Range ........................................................... 50 to 600,000 ms
Accuracy....................................................................

±0.5% or ±2 cycles, whichever is greater

Specifications