Motor manufacturer data – Basler Electric BE1-11m User Manual

Page 528

Advertising
background image

516

9424200996 Rev L

Motor Manufacturer Data

Motor manufacturer data should be reviewed before configuring the BE1-11m. Typical motor
manufacturer data is listed below.

GENERAL

HP .................................................................. 2900

Full-Load Amps (FLA) ................................... 363

Maximum Locked Rotor Current (LRA) ......... 600%

Bus Voltage ................................................... 4 kV

Service Factor................................................ 1.0

Stator Insulation Class ................................... F (155

°C per NEMA MG-1 Standard)

Ambient Temperature Rating ........................ 40

°C

Stator Temperature Rise ............................... 80

°C

Subtransient Reactance Xd” .......................... 0.15 pu, 2432 kVA base

RTDs

Six Stator RTDs ............................................. 100

Ω, 3-wire element, platinum

Two Bearing RTDs ........................................ 100

Ω, 3-wire element, platinum

One Ambient RTD ......................................... 100

Ω, 3-wire element, platinum

STARTING

Minimum Starting Voltage ............................. 85%

Hot Safe Stall Time ........................................ 9 seconds

Cold Safe Stall Time ...................................... 10 seconds

Rotor WK

2

...................................................... 410 lb-ft

2

CONSECUTIVE STARTS

Ambient Temperature .................................... 3 starts

Idle Starts Time ................................ 45 minutes

Running Starts Time ......................... 20 minutes

Operating Temperature ................................. 2 starts

Idle Starts Time ................................ 45 minutes

Running Starts Time ......................... 45 minutes

THERMAL TIME CONSTANT

Ambient (Stopped Condition) ........................ 75 minutes

Operating (Running Condition) ...................... 60 minutes

RUNNING

Ride Through Minimum Voltage .................... 75% for 60 seconds

Bearing Alarm Temperature .......................... 90

°C

Bearing Trip Temperature ............................. 95

°C

OPERATING PERFORMANCE

Load % ........................................................... 100 ...... 75 ........ 50

Amps .............................................................. 363 ...... 276 ...... 190

Efficiency % ................................................... 95.5 ..... 95.3 ..... 94.7

PF .................................................................. 90 ........ 89 ........ 87

OTHER

Name

Location

System Frequency

System Rotation

Settings Calculation Examples

BE1-11m