Table 21. Logic Inputs and Outputs

Name

Logic Function

Purpose

Block

Input

Disables the 50BF function when true

50BFI

Input

Starts the 50BF timer when true

52BFI

Input

Starts the 50BF timer when true

Trip

Output

True after the 50BF Delay Timer expires

ReTrip

Output

True when the 50BF Delay Timer is actively timing

Operational Settings

Breaker failure element operational settings are configured on the Breaker Fail (50BF) settings screen
(Figure 47) in BESTCOMSPlus. Settings ranges and defaults are summarized in Table 22.

Figure 47. Breaker Fail Settings Screen

Table 22. Operational Settings

Setting

Range

Increment Unit of Measure

Default

Mode

Disabled or Enabled

n/a

n/a

Disabled

Source

*

CT Circuit1 or CT Circuit 2

n/a

n/a

CT Circuit 1

Pickup (Phase & Ground)

0 or 0.25 to 10.00 (5A CTs)

0 or 0.05 to 2.00 (1A CTs)

0 or 0.01 to 0.5 (SEF)

varies

amps

0

Control Timer

0 or 50 to 999

varies

milliseconds

50

Delay Timer

0 or 50 to 999

varies

milliseconds

50

* For protection systems equipped with two sets of CTs.

BE1-11m

Breaker Failure (50BF) Protection