Functional test report, Pickup verification, Timing verification – Basler Electric BE1-11m User Manual

Page 397

Advertising
background image

9424200996 Rev L

385

Step 2: Prepare to monitor the 40Q timings. Timing accuracy is verified by measuring the elapsed time

between a sensing current change and OUT1 closing.

Step 3: Connect and apply a 100 Vac, three-phase voltage source to terminals C13 (A-phase), C14 (B-

phase), C15 (C-phase), and C16 (Neutral). Connect and apply a 4.5 A current source (that is in
phase with the voltage) to terminals D1 (A-phase polarity) and D2 (A-phase non-polarity).

Step 4: Step the A-phase current up to 5.5 amps. Measure the time delay and record the result.

Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delay settings of Table 171. Record the

results.

Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3.

Functional Test Report

Pickup Verification

Pickup Setting Range = 1 to 6,000 var for 5A sensing

1 to 1,200 var for 1A sensing

Pickup Accuracy =

±3% or ±2 var, whichever is greater

Dropout should occur between 95-99% of the actual pickup value.

Step

Pickup

Setting

Low

Actual

Pickup

High

Low

*

Actual

Dropout

High

*

Pass/Fail

5

500 var

485 var

515 var

475 var

495 var

P / F

7

1,000 var

970 var

1,030 var

950 var

990 var

P / F

7

2,000 var

1940 var

2,060 var

1,900 var

1,980 var

P / F

* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.

Timing Verification

Time Delay Range = 1 to 600,000 ms

Timing Accuracy =

±0.5% or ±2 cycles, whichever is greater

Step

Time Delay Setting

Low

Actual Timing

High

Pass/Fail

4

2,000 ms

1,968 ms

2,032 ms

P / F

5

5,000 ms

4,968 ms

5,032 ms

P / F

5

10,000 ms

9,950 ms

10,050 ms

P / F

BE1-11m

Loss of Excitation - Reverse Var Based (40Q) Test

Advertising