Remote rtd, Module – Basler Electric BE1-11m User Manual

Page 568

Advertising
background image

556

9424200996 Rev L

Figure 391. Motor Differential Connection Example

This example uses percent differential mode. The motor must have all six stator leads brought out so that
CTs can be placed on the input and output leads of each stator winding.

The six CTs have matching characteristics, and for smaller operation currents (during running mode),
Restraint Slope 1 % can be less. However, during the starting mode, CT saturation is large. As a security
measure, choose a large Restraint Slope 2 % to avoid false trips during starting.

Set the Minimum Restrained Pickup to 0.1 for maximum differential sensitivity, which provides optimal
motor protection. This setting is in per units of tap. The minimum pickup current sensitivity is calculated in
Equation 72.

π‘€π‘–π‘›π‘–π‘šπ‘’π‘š π‘ƒπ‘–π‘π‘˜π‘’π‘ πΆπ‘’π‘Ÿπ‘Ÿπ‘’π‘›π‘‘ 𝑆𝑒𝑛𝑠𝑖𝑑𝑖𝑣𝑖𝑑𝑦 = 𝑇𝐴𝑃 βˆ™ π‘€π‘–π‘›π‘–π‘šπ‘’π‘š π‘…π‘’π‘ π‘‘π‘Ÿπ‘Žπ‘–π‘›π‘’π‘‘ π‘ƒπ‘–π‘π‘˜π‘’π‘ = 2.0 βˆ™ 0.1 = 0.2 𝐴

Equation 72. Minimum Pickup Current Sensitivity

CT Circuit 1 Tap and CT Circuit 2 Tap are shown here, but calculated from the System Parameters,
Sensing Transformers screen (Figure 372). With equal CT ratios, the secondary currents through the
BE1-11m restraint algorithm for external faults and load are similar, and the operating current is very
small. If the differential CTs do not match, use the TAP settings on the System Parameters, Sensing
Transformers screen to balance the differential.

Running Slope

In running mode, the differential can be more sensitive, yet provide security and reliability at 15 percent as
described by IEEE C37.96-2000, IEEE Guide for AC Motor Protection. Set the Restraint Slope 1 %
setting to 15.

Starting Slope

The BE1-11m considers the motor to be starting when current is greater than 2

β€’ FLA in any phase. The

starting mode ends when current in all three phases drops below 2

β€’ FLA. Therefore, the 2

nd

Slope Pickup

(starting) should be set at the point that restraint current is 2

β€’ FLA where motor torques and heating

settle quickly to running mode currents (as observed in typical time-current curves). See Equation 73.

2𝑛𝑑 π‘†π‘™π‘œπ‘π‘’ π‘ƒπ‘–π‘π‘˜π‘’π‘ πΆπ‘’π‘Ÿπ‘Ÿπ‘’π‘›π‘‘ = 𝐹𝐿𝐴 βˆ™

1

𝐢𝑇𝑅

βˆ™ 2 = 205 βˆ™

1

60

βˆ™ 2 = 6.83 𝐴

2𝑛𝑑 π‘†π‘™π‘œπ‘π‘’ π‘ƒπ‘–π‘π‘˜π‘’π‘ 𝑆𝑒𝑑𝑑𝑖𝑛𝑔 =

6.83

2.0 = 3.42 𝐴

M

A

1

I

A

1

β€’

A

2

I

A

1

A

3

I

B

1

β€’

A

4

I

B

1

A

5

I

C

1

β€’

A

6

I

C

1

B

5

I

C

1

β€’

B

6

I

C

1

B

1

I

A

2

β€’

B

2

I

A

2

B

3

I

B

2

β€’

B

4

I

B

2

Remote RTD

Module

BE

1

-

11

m

/

6

Stator RTDs

/

2

Bearing RTDs

/

1

Ambient RTDs

RJ

-

45

RJ

-

45

A

B

C

Settings Calculation Examples

BE1-11m

Advertising