Table 112. Operational Settings (V2 Mode)

Setting

Value

BESTCOMSPlus Screen

Description

Phase VT Ratio

1

System Parameters, Sensing
Transformers

Sets phase VT ratio to 1

Phase VT
Connection

4W-Y

System Parameters, Sensing
Transformers

Sets phase VT connection to
4W-Y

27/59 Mode

PN

System Parameters, Sensing
Transformers

Sets 27/59 mode to phase-
neutral

Element Mode

V2

Protection, Voltage, Overvoltage
(59X-1)

Enables 59X-1 function for V2
mode

Timing Mode

Definite

Protection, Voltage, Overvoltage
(59X-1)

Selects definite timings

59X-1 V2

Enabled Target Configuration, Targets

Enables V2 target for 59X-1

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 245.

Blocking is disabled.

OUT1 closes for 59X-1 Trip.

OUT2 closes for 59X-1 Pickup.

Fault recording is enabled.

Figure 245. BESTlogicPlus Settings (V2 Mode)

Step 3: Use BESTCOMSPlus to open the Protection, Voltage, Overvoltage (59X-1) screen and send

the first row of test settings in Table 113 to the BE1-11m.

Table 113. Pickup Test Settings (V2 Mode)

Pickup Setting

Time Delay

82 V

50 ms

42 V

50 ms

25 V

50 ms

Step 4: Prepare to monitor the 59X-1 function operation. Operation can be verified by monitoring OUT2

(see Figure 245).

Step 5: Connect and apply a 240 Vac, single-phase voltage source to terminals C13 (A-phase) and C16

(neutral). For a single-phase input test, V2 = A-phase voltage / 3. Therefore, the BE1-11m
should pick up at a value of three times the setting value when applying only a single-phase
input. For example, to determine the pickup voltage value required for a BE1-11m with a pickup
setting of 82, it would require 82 times 3 or 246 volts of input voltage.

Step 6: Slowly increase the voltage until OUT1 closes and record the pickup. Verify that there is a 59X-

1-V2 target on the front-panel display. Slowly decrease the voltage until OUT1 opens and
record the dropout. Reset the target.

BE1-11m

Auxiliary Overvoltage (59X) Test