Functional test report, Timing verification – Basler Electric BE1-11m User Manual

Page 417

Advertising
background image

9424200996 Rev L

405

Step 7: Apply 10 Aac three-phase current for approximately one minute (simulate motor starting). Note

that this is the second start. Verify that OUT1 (Starting) and OUT3 (Start Blocked) close and
OUT 2 (Stopped) opens.

Step 8: Remove three-phase current. Verify that OUT1 (Starting) opens and OUT2 (Stopped) closes.

Verify that OUT3 (Start Blocked) remains closed.

Step 9: Wait approximately three minutes for timing to complete. Stop the timer when OUT4 (Start

Block Removed) closes and record the time. The expected timing is 360 seconds (6 minutes).
Note that OUT3 (Start Blocked) opens when OUT4 (Start Blocked Removed) closes.

Functional Test Report

Timing Verification

Time Interval Range = 1 to 1,440 min

Timing Accuracy =

±0.5%

Step

Time Interval

Low

Actual Timing

High

Pass/Fail

9

360 s (6 min)

358.2 s

361.8 s

P / F

BE1-11m

Starts per Time Interval (66) Test