Forward tripping direction (overpower) – Basler Electric BE1-11m User Manual

Page 390

Advertising
background image

378

9424200996 Rev L

Setting

Value

BESTCOMSPlus Screen

Description

32-1 A Over

Enabled Target Configuration,

Targets

Enables phase A over target for 32-1

32-1 A Under

Enabled Target Configuration,

Targets

Enables phase A under target for 32-1

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus Programmable Logic shown in Figure

264.

Blocking is disabled.

OUT1 closes for 32-1 Trip.

OUT2 closes for 32-1 Pickup.

Fault recording is enabled.

Figure 264. BESTlogicPlus Settings

Forward Tripping Direction (Overpower)

Step 1: Using Table 165 as a guide, send the 32-1 settings to the BE1-11m. Prior to each directional

test, reset the BE1-11m targets from the previous test.

Table 165. Forward-Overpower Test Settings

Pickup

Direction

Over Under

500 W

Forward

Over

1000 W

Forward

Over

2000 W

Forward

Over

Step 2: Connect and apply a 100 Vac, three-phase voltage source at nominal frequency to terminals

C13 (A-phase), C14 (B-phase), C15 (C-phase), and C16 (neutral). Connect a variable ac
current source to terminals D1 (A-phase polarity) and D2 (A-phase non-polarity).

Step 3: Set A-phase current in phase with the voltage and slowly increase the current from 0 amps until

OUT2 closes and record the pickup. Verify that there is a 32-1-A-Over target on the front-panel
display. Decrease A-phase current until OUT2 opens and record the dropout. Pickup will occur
within

±3% of the three-phase 32-1 pickup setting divided by 3 (500 watts = 5 amps, 100 volts, 0

degrees lag E)/3. See the Power Protection (32) chapter for details on single phase and total
power operation.

Step 4: With the BE1-11m picked up (OUT2 closed), change the angle of the applied current to lag the

voltage by 180 degrees and verify that OUT2 opens. This verifies that the 32-1 function is
operating in the forward trip direction and not in the reverse direction.

Step 5: Repeat steps 1 through 4 for the 1,000 W and 2,000 W pickup settings in Table 165. Record the

results.

Step 6: (Optional.) Repeat steps 1 through 5 for B-phase and C-phase currents. (Consult the Power

(32) Protection chapter for operating details).

Step 7: (Optional.) Repeat steps 1 through 6 for settings group 1, 2, and 3.

Power (32) Test