55

Table 17. Operational Settings

Setting

Range

Increment

Unit of Measure

Default

Mode

Disabled or 3 Phase

n/a

n/a

Disabled

Source

*

CT Circuit 1 or CT Circuit 2

n/a

n/a

CT Circuit 1

Pickup

0 or 0.5 to 100 (5A CTs)

0 or 0.1 to 20 (1A CTs)

varies

amps

0

Inhibit Level

0 or 0.5 to 100 (5A CTs)

0 or 0.1 to 20 (1A CTs)

varies

amps

0

Time Delay

0 to 60,000

varies

milliseconds

0

* For protection systems equipped with two sets of CTs.