Time delay verification (roc frequency), Inhibit quantities (roc inhibit) – Basler Electric BE1-11m User Manual

Page 343

Advertising
background image

9424200996 Rev L

331

Step 4: Connect a 120 Vac voltage source capable of smoothly sweeping the frequency from 35 Hz to

75 Hz to terminals C13 (A-phase) and C16 (neutral).

Step 5: Set the ramp rate at 0.001 seconds/step (max level, lower if possible) and set the total number

steps at 1,000 (one second total for the sweep test).

Step 6: Set the frequency range of the sweep (ramp) for 55.0 to 64.7 Hz. This equates to a ROC of 9.7

Hz/sec (3.0% below the 10.0 Hz/sec pickup setting).

Step 7: Initiate the sweep (ramp) which simultaneously applies voltage to the BE1-11m and note that

there is no operation of OUT2.

Step 8: Increase the rate of change in increments of 1% (9.8, 9.9 Hz/sec) up to 9.9 Hz/sec and 0.5%

thereafter until OUT2 closes and record the pickup.

Step 9: Repeat steps 3 through 8 with the pickup value set at 2 Hz/sec. Begin the test by applying a

rate of change value 8% below pickup (1.84 Hz/sec or a frequency sweep range of 59 to 60.84
Hz). Increase the rate of change in 1% increments until OUT2 closes and record the pickup.

Step 10: (Optional.) Repeat steps 1 through 9 in Positive ROC mode. Additionally, verify that a sweep

from a high to low frequency does not cause an operation.

Step 11: (Optional.) Repeat steps 1 through 9 in Negative ROC mode by reversing the sweep rate from

high to low to simulate negative rate of change. Additionally, verify that a sweep from a low to
high frequency does not cause an operation.

Step 12: (Optional.) Repeat steps 1 through 11 for settings group 1, 2, and 3.

Step 13: (Optional.) Repeat steps 1 through 12 for 81-2, 81-3, and 81-4.

Time Delay Verification (ROC Frequency)

Time delay verification is not necessary for the ROC mode as the same timers are used as in the
over/underfrequency timing tests. Timing starts when the 81 Pickup goes high whether the cause is over,
under, or rate of change.

Inhibit Quantities (ROC Inhibit)

Operation in the rate of change mode can be inhibited by sensing voltage, negative-sequence voltage,
and frequency limits or range, the latter of which creates a “frequency window” of operation. The sensing
voltage inhibit is the same feature used for the over/underfrequency elements and has already been
tested. The following tests verify the negative-sequence and frequency limit inhibits.

Step 1: Use the Settings Explorer in BESTCOMSPlus to open the Protection, Frequency, Frequency

(81-1) screen and send the operational settings in Table 127 to the BE1-11m.

Table 127. Operational Settings (ROC Inhibit)

Setting

Value

Description

Element Mode

Rate of Change

Enables 81-1 function for Rate of Change mode

Source

Phase VT

Sets source to Phase VT

Pickup

2 Hz/sec

Sets pickup to 2 Hz/sec

Time Delay

0 ms

Sets time delay to minimum

Voltage Inhibit

40 V

Sets voltage inhibit pickup to 40 V

Over Frequency Inhibit

64 Hz

Sets overfrequency inhibit to 64 Hz

Under Frequency Inhibit

46 Hz

Sets underfrequency inhibit to 46 Hz

Negative Sequence Inhibit

20%

Sets negative-sequence inhibit to 20%


BE1-11m

Frequency (81) Test

Advertising