Timing verification (phase mode), N figure 259 – Basler Electric BE1-11m User Manual

Page 368

Advertising
background image

356

9424200996 Rev L

Figure 259. BESTlogicPlus Settings (Phase Mode)

Step 3: Use BESTCOMSPlus to open the Protection, Current, Inverse Overcurrent (51-1) screen and

send the low range test settings (minimum pickup setting) to the BE1-11m for your sensing input
type in Table 147.

Table 147. Pickup Test Settings (Phase Mode)

Sensing Input

Type

Range

Pickup Setting

Time Dial

Time Curve

5 A

Low

0.5 A

0

I2

Middle

5.0 A

0

I2

High

16.0 A

0

I2

1 A

Low

0.1 A

0

I2

Middle

1.0 A

0

I2

High

3.2 A

0

I2

Step 4: Prepare to monitor the 51-1 function operation. Operation can be verified by monitoring OUT2

(see Figure 259).

Step 5: Connect a current source to terminals D1 and D2 (A-phase). Note that mode can be set for IA,

IB, IC, or 3 phases. Test is conducted on IA.

Step 6: Slowly increase the A-phase current until OUT2 closes and record the pickup. Verify that there

is a 51-1-A target on the front-panel display. Slowly decrease the applied current until OUT2
opens and record the dropout.

Step 7: Repeat step 6 for the middle and high range pickup settings for your sensing input type. Record

the results.

Step 8: (Optional.) Repeat steps 1 through 7 for phase B and phase C. Note: Be sure to change

Element Mode and enable proper target for each phase being tested.

Step 9: (Optional.) Repeat steps 1 through 8 for settings group 1, 2, and 3.

Step 10: (Optional.) Repeat steps 1 through 9 for 51-2, 51-3, 51-4, and 51-5.

Step 11: (Optional.) Repeat steps 1 through 10 with CT Circuit 2 as the source for protection systems

equipped with two sets of CTs. In step 5, replace D1 with F1, D2 with F2, etc.

Timing Verification (Phase Mode)

Step 1: Use BESTCOMSPlus to open the Protection, Current, Inverse Overcurrent (51-1) screen and

send the test settings in Table 148 to the BE1-11m for settings group 0.

Table 148. Timing Test Settings (Phase Mode)

Pickup Setting

Time Curve

0.5 A (5 A sensing), 0.1 A (1 A sensing or SEF)

I2

Inverse Overcurrent (51) Test