Instantaneous overcurrent (50) protection, Element operation, Modes of protection – Basler Electric BE1-11m User Manual

Page 71: Instantaneous overcurrent, Protection

Advertising
background image

9424200996 Rev L

59

Instantaneous Overcurrent (50)
Protection

Six instantaneous overcurrent (50) elements monitor the current applied to the BE1-11m. An element can
be configured to protect against overcurrent by monitoring a single- or three-phase system, neutral
current, positive-sequence current, negative-sequence current, ground current, or unbalanced current.

The six, identical instantaneous overcurrent protection elements are designated 50-1, 50-2, 50-3, 50-4,
50-5, and 50-6. Element logic connections are made on the BESTlogicPlus screen in BESTCOMSPlus
and element operational settings are configured on the Instantaneous Overcurrent settings screen in
BESTCOMSPlus. A summary of the logic inputs and outputs and operational settings appears at the end
of this chapter.

BESTCOMSPlus Navigation Path: Settings Explorer, Protection, Current, Instantaneous Overcurrent
(50)

HMI Navigation Path: Settings Explorer, Protection, Settings Group x (where x = 0 to 3), Current
Protection, Instant Overcurrent 50

Element Operation

Instantaneous overcurrent protection can be used to protect equipment from damage caused by phase
failure, forward/reverse phase sequence, or phase unbalance.

Modes of Protection

Nine modes of protection are available: IA, IB, IC, Three-Phase, 3I0, I1, I2, IG, and Unbalance.

IA, IB, or IC Mode

The instantaneous overcurrent protection elements include three independent comparators, one for each
phase. Mode selection determines which phase pickup is required to activate protection.

Three-Phase Mode

The instantaneous overcurrent protection elements include three independent comparators, one for each
phase. Protection is activated when any of the three phases increases above the Pickup setting.

3I0 Mode

3I0 mode provides neutral overcurrent protection in a three-phase system.

I1 Mode

I1 mode provides positive-sequence overcurrent protection in a three-phase system.

I2 Mode

I2 mode provides negative-sequence overcurrent protection in a three-phase system. Refer to the

Negative-Sequence Overcurrent (46) Protection

chapter for more information.

IG Mode

IG mode provides ground fault protection in a three-phase system.

Unbalance Mode

Unbalance mode provides unbalanced current protection. Two methods are available to calculate
unbalanced current. The first method is based on the negative-sequence current divided by the positive-
sequence current while the second method is based on the average current. The calculation method must

BE1-11m

Instantaneous Overcurrent (50) Protection

Advertising