Functional test report, Pickup verification, Timing verification – Basler Electric BE1-11m User Manual

Page 349

Advertising
background image

9424200996 Rev L

337

Step 2: Prepare to monitor the 37 timings. Timing accuracy is verified by measuring the elapsed time

between a sensing current change and OUT1 closing.

Step 3: Connect a current source and apply 0.55 Aac to terminals D1 and D2 (A-phase).

Step 4: Step the current down to 0.45 A. Measure the time delay and record the result.

Step 5: Repeat step 4 for the 5000 ms and 10000 ms time delay settings of Table 130. Record the

results.

Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3.

Step 7: (Optional.) Repeat steps 1 through 6 with CT Circuit 2 as the source for protection systems

equipped with two sets of CTs. In step 3, replace D1 with F1, D2 with F2, etc.

Functional Test Report

Pickup Verification

Pickup Setting Range = 0.5 to 100 A for 5A sensing

0.1 to 20 A for 1A sensing

Pickup Accuracy =

±2% or ±50 mA, whichever is greater for 5A sensing

±2% or ±10 mA, whichever is greater for 1A sensing

Dropout should occur between 101-107% of the actual pickup value.

Step

Pickup Setting

Low

Actual Pickup

High

Low

*

Actual Reset

High

*

Pass/Fail

6

0.5 A (5A CT)

0.45 A

0.55 A

0.505 A

0.535 A

P / F

7

5.0 A (5A CT)

4.9 A

5.1 A

5.05 A

5.35 A

P / F

7

20.0 A (5A CT)

20.6 A

20.4 A

20.2 A

21.4 A

P / F

6

0.1 A (1A CT)

0.09 A

0.11 A

0.101 A

0.107 A

P / F

7

1.0 A (1A CT)

0.98 A

1.02 A

1.01 A

1.07 A

P / F

7

4.0 A (1A CT)

3.92 A

4.08 A

4.04 A

4.28 A

P / F

* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.

Timing Verification

Time Delay Range = 0 to 60000 ms

Timing Accuracy =

±0.5% or ±½ cycle, whichever is greater + 3 cycles max for currents 1.5 x pickup

Step

Time Delay Setting

Low

Actual Timing

High

Pass/Fail

4

2000 ms

1942 ms

2058 ms

P / F

5

5000 ms

4927 ms

5073 ms

P / F

5

10000 ms

9902 ms

10098 ms

P / F

BE1-11m

Instantaneous Undercurrent (37) Test

Advertising