9424200996 Rev L

17

Figure 12. Instantaneous Overcurrent (50-4) Screen

Figure 13. BESTlogicPlus Logic Page 3

Step 10: In this step, the Pickup output of the 50-4 element is connected to Output 4. When the Pickup

output of the 50-4 element is true, the label of Output 4 is displayed in the fault report and/or
sequence of events report. The label is named in Step 12. Click the Logic Page 3 tab and then
click the I/O tab at the bottom. Expand Output Objects and then Physical Outputs. Click and
drag OUT4 over to the logic diagram. Click on the Pickup output of the 50-4 element and drag it
to the input of OUT4 to make a connection. Refer to Figure 15.

BE1-11m

Quick Start