Figure 70), N table 39 – Basler Electric BE1-11m User Manual

Page 113

Advertising
background image

9424200996 Rev L

101

Figure 70. Thermal Curve Settings Screen

Table 39. Operational Settings

Setting

Range

Increment

Unit of

Measure

Default

Mode

Disabled, Standard Curve, IEC

Curve, or User Curve

n/a

n/a

Disabled

RTD Biasing

*

Disabled or Enabled

n/a

n/a

Disabled

RTD Source

*

RTD Group 1 to RTD Group 4

n/a

n/a

RTD

Group 1

Standard Curve

Time Dial

1 to 20

0.01

units

1

K

0 to 20

0.01

units

1

IEC Hot Curve Current

0 to 25 (5A CTs)

0 to 5 (1A CTs)

0.001

amps

0

IEC Curve

Time Constant

1 to 10,000

1

seconds

1

Overload

0.9 to 1.2

0.01

units

1

Max Emergency

Thermal Capacity

0 or 150 to 1,000

1

percent

0

Running Cool

Time Constant

1 to 1,000

0.01

minutes

1

Stopped Cool

Time Constant

1 to 1,000

0.01

minutes

1

Hot Safe Stall Time

1 to 2,000

0.1

seconds

0

Cold Safe Stall Time

1 to 2,000

0.1

seconds

0

* For use when an optional RTD module is connected.

BE1-11m

Thermal Curve (49TC) Protection