Basler Electric BE1-11m User Manual

Page 18

Advertising
background image

6

9424200996 Rev L

Breaker Failure (50BF) Protection

One breaker failure function provides protection and security for the power system against failure of the
monitored breaker.

Inverse Overcurrent (51) Protection

Five inverse overcurrent elements can be set for single-phase, three-phase, ground, neutral, positive-
sequence, negative-sequence, or unbalanced protection. Inverse-overcurrent functions employ a dynamic
integrating timing algorithm covering a range from pickup to 40 times pickup with selectable
instantaneous or integrated reset characteristics. Inverse time overcurrent curves conform to IEEE Std
C37.112-1996 - IEEE Standard Inverse-Time Characteristic Equations for Overcurrent Relays, and
include seven curves similar to Westinghouse/ABB CO curves, five curves similar to GE IAC curves, a
fixed time curve, and a user programmable curve. Refer to the

Time Curve Characteristics

chapter for

more information about the inverse overcurrent protection characteristic curves.

Negative-sequence current protection (46) is included as a mode of the 51 (inverse overcurrent) element.
Each inverse overcurrent element can be individually set for forward, reverse, or non-directional control.

A separate ground current input provides ground overcurrent protection for a separate ground CT.
Optionally, an SEF (sensitive earth fault) version of the separate ground CT is available.

Phase Current Differential (87) Protection

One phase current differential element provides three-phase, percentage-restrained, differential
protection with dual-slope, in-phase, differential mode. In flux balance mode, the differential CTs are
connected in a flux balancing configuration.

Power (32) Protection

A directional power element can be set for forward or reverse, overpower or underpower protection. The
element can be used for any application requiring directional power flow detection including intertie
protection (interconnects between an electric utility and a source of non-utility generation). The power
measurement algorithm is adapted as appropriate for any possible three-phase or single-phase voltage
transformer connection. Directional power is calibrated on a three-phase basis regardless of the voltage
transformer connection used. Directional Power Protection can be set for one of three, two of three, three
of three, or total power.

Note

BE1-11m protection systems enabled for IEC-61850 communication
(style Mxxxx5xxxxxxxx) have their power protection elements fixed at
one underpower element.

Loss of Excitation - Reverse Var Based (40Q) Protection

One loss of excitation element operates on excessive var flow into the machine, indicating abnormally low
field excitation.

Power Factor (55) Protection

A power factor element protects synchronous motors from receiving vars from the external power system
due to loss of field excitation.

Thermal Curve (49TC) Protection

A thermal curve element provides thermal protection of the motor with a current-based thermal model that
includes unbalanced current biasing, custom voltage-dependent curves, RTD biasing, and emergency
start override.

Introduction

BE1-11m

Advertising