Frequently Asked Questions (FAQ)

Electrical/Connections

Is the power supply polarity sensitive?

No, the power supply will accept either an ac or dc voltage input. Refer to the

Typical Connections

chapter.

Are the sensing contacts polarity sensitive?

Yes, refer to the

Typical Connections

chapter for more information.

What voltage level is used to develop current flow through the contact sensing inputs?

Voltage level is dependent on the power supply option (called out in the BE1-11m style chart). For
additional information, refer to the

Contact Inputs and Outputs

chapter and the style chart in the

Introduction

chapter.

Can the IRIG signal be daisy-chained to multiple BE1-11m units?

Yes, multiple BE1-11m units can use the same IRIG-B input signal by daisy-chaining the BE1-11m inputs.
The burden data is nonlinear, approximately 4 kilo-ohms at 3.5 Vdc and 3 k

Ω at 20 Vdc. See the

Specifications

chapter for additional information.

General Operation

Does the BE1-11m trip output contact latch after a fault?

The answer to the question is yes and no. In general, once the fault goes away the output contacts open.
The BE1-11m does offer an option to ensure that the contact will stay closed for at least 200 milliseconds.
See the

Contact Inputs and Outputs

chapter for additional information on that function. Also, a Set Priority

Latch in BESTlogic

Plus can keep the relay outputs closed as long as power is applied.

Can I make logic settings at the front panel?

No, logic settings cannot be made at the front panel. Logic settings must be programmed using
BESTCOMSPlus

® communication software.

Since the BE1-11m is a programmable device, what are the factory defaults?

Default settings are shown with each function in the instruction manual. For input or output default
settings see the

Contact Inputs and Outputs

chapter. For protection and control functions, see the

appropriate chapters. The factory default logic scheme is defined in the

BESTlogicPlus

chapter.

Does the BE1-11m have a battery installed as the backup power source for the internal
clock on loss of power?

A ride-through capacitor, up to 24 hours, and a backup battery, greater than five years, are standard
features of the BE1-11m. Refer to the

Timekeeping

chapter for more information on the backup battery

including replacement.

How are reports and other information obtained from the BE1-11m saved in files for
future use?

BESTCOMSPlus can be used to view sequence of events, fault records, security log, load profile, and
breaker status. See the appropriate chapters for more information.

BE1-11m

Frequently Asked Questions (FAQ)