524

9424200996 Rev L

Figure 348. Standard Curves

RTD Bias Curve

The RTD bias curve includes a minimum of three points and a maximum of 40 points. Three typical points
are defined at Minimum RTD Bias Temperature, Center RTD Bias Temperature, and Maximum RTD Bias
Temperature. The BE1-11m can use the standard 3-point biasing, and you can add as many as 40
biasing points for better thermal modeling and protection at high-temperature operation.

Set the Minimum RTD Bias Temperature (point 1) at ambient (40

°C) and 0 percent thermal capacity as

shown in Figure 349.